Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A

Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A
Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A Auto / Remote Starter Kit for Generator MEP 004A / 005A / 006A
Brand: INOVA HIGHTECH Ltd.
Product Code: MEPKIT004A/005A/006A
Availability: 2 - 3 Days
Price: $389.95

3 or more $359.95

Available Options


Time Delay OFF Relay Kit " K ext. " MEP X03/4/5/6:

* Wire Type:

Qty:     - OR -   Add to Wish List
Add to Compare

The INOVA HIGHTECH MEP 004A / 005A / 006A Autostarter Kit is a great add on for your MEP Generator Set. It will allow remote start with the flip off a switch or it can be connected to an Automatic Transfer Switch.

INOVA HIGHTECH MEP 005A Autostarter Kit installed by our customer Richard Sanderson II of Clear Communications, Inc. in New Orleans, who was also so kind to provide us with these two videos, in conjunction with a Cumins Power Command ATS to provide Emergency Backup for his business Clear Communications, Inc.


 

 


Installation / Operating Manual:
 

 

The Autostarter Board KIT for the 004A/005A/006A is the same as for the 002A/003A

 

Except that the 004A/005A/006A version has a different Software loaded!

 

The 004A/005A/006A Software affects/changes the following functions / Terminal Nomenclature:

 

1.             Dip Switch Functions, Settings and Timing

2.             Different Connections between the Board and the Cubicle

3.             No external Contactor needed [utilizing internal CB2]

4.             No Pre Heat - Pre Heat Output is used for Ether Injection instead

5.             Ether Injection selectable On/Off with 5 sec or 15 sec of injection time

                Select Ether Injection only if your Ether system is working correctly!

6.             No ambient temperature dependent timing

7.             The Aux Fuel Output is now used to fill the Day Tank for 30 or 60 seconds and to pressurize the fuel system

8.             The RUN/PRIME Output is now only a RUN OUTPUT

9.             The Oil P / TEMP Input will now additionally monitor Over Voltage and Low Fuel, besides Oil Pressure and Over Temperature

All other instructions from the MEP 002A/003A Manual apply for these Gen Sets as well

 


The MEP 004A / 005A / 006A Autostarter has the following features which can be set with the DIP Switch on the Board:

DIP Switch Settings 004A / 005A / 006A

DIP SWITCH

Function

DIP SWITCH ON POSITION

DIP SWITCH OFF POSITION

1

DAY TANK FILL (Prime)

1 min (60 sec)

30 sec

2

Warm Up

5 min (300 sec)

1 min (60 sec)

3

Cool Down

DIP2 OFF 06 min (360 sec)

DIP2 ON 10 min (600 sec)

DIP2 OFF 02 min (120 sec)

DIP2 ON 06 min (360 sec)

4

Ether Injection

YES

NO

5

Ether Injection Time

15 sec

5 sec


The Autostarter will automatically shut down and display a light indicator in the event of a Low Oil Pressure, Overheat, Over Voltage and Low Fuel situation, preventing the Generator Set from automatically restarting. The Autostarter can easily be reset, once the issues of leading to Low Oil Pressure, Overheat, Over Voltage and Low Fuelsituation have been fixed/corrected.

The installation requires a working knowledge of the MEP 004A/005A Electrical System.

The MEP 004A / 005A / 006A Autostarter KIT includes:

1. MEP 004/005/006 Autostarter Circuit Board
2. MIL-I-46058C Conformal Coating
3. Drill / Mounting Templates
4. Detailed Installation Manual
5. 15 feet 16ga standard multi stranded SXL wire, strong resistance to moisture, solvents and prolonged high heat -
    Thick wall special purpose automotive wire is insulated with chemically cross-linked polyethylene. Withstands prolonged temperatures of up to 257°F
6. Mounting Hardware [Stainless Steel Phillips Pan Head Machine Screws #6-32x0.75", Stainless Steel #6-32 Nuts as Spacers, Stainless Steel #6-32 K-Lock Nut's]
7. Crimp On Fork and Ring Lugs
8. Wiring Diagram
9. A 60 Day Money Back Guarantee
10. 1 Year Limited Warranty
11. 15 Amp Diode
12. Toggle On / Off Switch

MEP004A installation Pictures of our Board Kit as courtesy of our Valued Customer AL HEIDEMANN of LODI, WI who installed one of our MEP 004A/005A/006A Autostarter Kits on his MEP004A Generator Set.
Al was instrumental in making this Kit possible for the MEP 004A/005A/006A Series! Thanks Al!


Videos of a MEP003A installation:
Contactor + Generator Start

Simulated Low Oil Pressure PART 1

Simulated Low Oil Pressure PART 2

EXTERNAL CONTACTOR

Transfer Switch
 

Write a review

Your Name:


Your Review: Note: HTML is not translated!

Rating: Bad           Good

Enter the code in the box below:



Powered By OpenCart
INOVA HIGHTECH Ltd. © 2018